ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean pit and cartop
|
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Provide testing of OSV, leave written procedures on sit, tag and seal upon completion
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.5 Illuminated Visual Signal
|
x
|
|
When the car is at the main recall floor with the doors open, the hall Fire Hat does not illuminate when Ph1 is activated.
|
|