Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.5 Illuminated Visual Signal Yes No When the car is at the main recall floor with the doors open, the hall Fire Hat does not illuminate when Ph1 is activated. 1/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Clean pit and cartop 1/23/2026
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No Provide testing of OSV, leave written procedures on sit, tag and seal upon completion 1/23/2026