Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Complete FFS wiring in machine room, and test all devices. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone working, but showing an incorrect address for the location. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lights and alarm not working. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine room fire extinguisher has no date tag.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Could not verify operation of battery lowering system. 4/14/2023
MO Minimum : Elevators (I) - Pits (I)8 Provide a non combustable cover for sump pump in pit.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Cannot confirm if smoke detectors are connected to the elevator controller. FFS recall & phase II tested by key, and worked. 4/14/2023