Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 Counterweight guide shoe is worn, EQ plate rubbing rail. Take corrective action as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 2/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Make machine room/overhead light operational. 12/13/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: Fire service testing log blank for 2022 & 2023.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 x Fire tabs are missing from the hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 1/13/2023