MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water in pit and sump pump is not working, sump pit is not covered & pit equipment is rusting
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
|
|
Landing sill is 1" above floor level creating tripping hazard
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
|
|
Landing sill is 1" above floor level creating a tripping hazard
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Sump pump in pit shall be operational.
|
2/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The sump pump in the pit shall be operational.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Remove fluids from the pit. The pit shall be kept clean and dry.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The sump pump in the pit shall be operational.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Remove fluids from the pit. The pit shall be kept clean and dry.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
|
|
Sump hole cover required to be flush with the pit floor. Cover is sitting on bricks
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Post Phase 1 fire service instructions near the fire service key switch in the lobby.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Replace missing firefighters Phase I signage at recall floor near keyswitch.
|
2/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Post Phase 1 fire service instructions near the fire service key switch in the lobby.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door not self closing/locking
|
5/15/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
2/9/2021
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Certificate of operation not on site
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
4/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency phone shall be operational with 24/7 support.
|
5/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The machine room door shall be self-locking.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The machine room door shall be self-locking.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.11.2.1.4(e)
|
|
|
The top floor lobby/hoistway access location has water leaking right outside the entrance to the elevator creating an unsafe condition for passengers and elevator personnel. The leak creating this hazard shall be reapaired.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.11.2.1.4(e)
|
|
|
The top floor lobby/hoistway access location has water leaking right outside the entrance to the elevator creating an unsafe condition for passengers and elevator personnel. The leak creating this hazard shall be reapaired.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.8 - Hoistway enclosure
|
8.11.2.1.4(h)
|
|
|
Repair the water leak in hoistway wall at top floor.
|
4/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
Smoke detectors at top landing are missing. Replace on or before Feb 8th to avoid elevator being red tagged.
|
2/17/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.2.7
|
x
|
|
Battery lowering unit is not working. Re-inspection required
|
7/23/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide current year tested fire extinguisher in the elevator machine room.
|
8/1/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher not tagged with expiration date
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher in machine room needs replacing or servicing.
|
2/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
The fire extinguisher in the machine room is expired and shall be serviced or replaced.
|
3/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
The fire extinguisher in the machine room is expired and shall be serviced or replaced.
|
3/31/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher is not tagged with expiration date
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.6.4.2
|
x
|
|
Govenor rope has rouge and sludge from water in pit. Replace and apply appropriate cable data tag
|
6/23/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Water in pit and sump pump is in-operable, no cover and pit equipment is rusting
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Equipment under water. Pit shall be kept clean and dry.
|
2/9/2021
|