Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Battery lowering unit is not working. Re-inspection required 7/23/2024
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Certificate of operation not on site 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 4/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Equipment under water. Pit shall be kept clean and dry. 2/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher in machine room needs replacing or servicing. 2/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is not tagged with expiration date 5/15/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher not tagged with expiration date 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 8.6.4.2 x Govenor rope has rouge and sludge from water in pit. Replace and apply appropriate cable data tag 6/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Landing sill is 1" above floor level creating a tripping hazard 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Landing sill is 1" above floor level creating tripping hazard 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door not self closing/locking 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 2/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Post Phase 1 fire service instructions near the fire service key switch in the lobby. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Post Phase 1 fire service instructions near the fire service key switch in the lobby. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Provide current year tested fire extinguisher in the elevator machine room. 8/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Remove fluids from the pit. The pit shall be kept clean and dry. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Remove fluids from the pit. The pit shall be kept clean and dry. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) Repair the water leak in hoistway wall at top floor. 4/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Replace missing firefighters Phase I signage at recall floor near keyswitch. 2/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Smoke detectors at top landing are missing. Replace on or before Feb 8th to avoid elevator being red tagged. 2/17/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Sump hole cover required to be flush with the pit floor. Cover is sitting on bricks 5/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Sump pump in pit shall be operational. 2/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 The fire extinguisher in the machine room is expired and shall be serviced or replaced. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 The fire extinguisher in the machine room is expired and shall be serviced or replaced. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone shall be operational with 24/7 support. 5/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The machine room door shall be self-locking. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The machine room door shall be self-locking. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The sump pump in the pit shall be operational. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The sump pump in the pit shall be operational. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) The top floor lobby/hoistway access location has water leaking right outside the entrance to the elevator creating an unsafe condition for passengers and elevator personnel. The leak creating this hazard shall be reapaired. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) The top floor lobby/hoistway access location has water leaking right outside the entrance to the elevator creating an unsafe condition for passengers and elevator personnel. The leak creating this hazard shall be reapaired. 3/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Water in pit and sump pump is in-operable, no cover and pit equipment is rusting 5/15/2024
MO Minimum : Elevators (I) - Pits (I)1 Water in pit and sump pump is not working, sump pit is not covered & pit equipment is rusting 5/15/2024