ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car "Help button" pushed in, repair and test phone.
|
9/30/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
TESTING INCOMPLETE due to Maint Co. scheduling conflicts and issues. REMAINING: all weight tests, buffer tests, slide,
|
9/30/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
There are no 5 yr test tags on elevator equipment. Re-inspection required
|
8/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.3 - Top-of-car operating device
|
8.11.2.1.3(c)
|
x
|
|
Car top inspection station does not work, needs repair. Re-inspection required Rule 2.26. 1.4.1 (A)
|
11/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(1) Wire ropes shall be replaced
|
x
|
x
|
Elevator has broken suspension cable, replace all cables. Red tagged, Re-inspection required Rule 8.6.3.2
|
11/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current State Operating Permit, expired
|
4/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Not Present: MCP, Testing procedures, Fire service log,
|
4/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
Hoistway access switch at top landing non-functional, Repair.
|
4/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
[1001.2(c)(29)]//8.6.1.6.2 : Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations. ( )
|
4/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
I(1) : Excessive debris in pit (combustible hazard)
|
4/11/2023
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
There are no 5 year test tags on elevator equipment. Have elevator company performed 5 year test to tag equipment
|
4/11/2023
|
A17.1-2016 : Elevators
|
3.3 - Top-of-car operating device
|
8.11.2.1.3(c)
|
|
|
Car top inspection does not work
|
4/11/2023
|