Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Car door restrictor shall work
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean pit and cartop
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The light bulbs shall have a cover on them to prevent glass from falling in case of breaking or shattering
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Repair car door restrictor. 3/7/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Firefighters Service is not working properly. The fire service hat light in the car flashes when on Phase II and should only flash when there is a fire in the machine room or hoistway. Re-inspection required 8/20/2024