Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x POWER BACK UP NOT WORKING / MISSING UNABLE TO LOWER UNIT WHEN POWER IS OFF
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x MUST MAKE ALARM OPERABLE
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x MUST MAKE AUXILIARY LIGHTS OPERABLE
conversion conversion n/a Must maintain car runby, Min. 6" currently 0". 10/14/2020
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post current state operating cert. 5.100(2) 10/5/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Must perform and document monthly fire service testing. 8.6.11.1 10/5/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Must provide current annual test tag on Mach. Room Fire Extinguisher. 8.11.2.1.2(j) 10/5/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Must provide and Maintain all required MCP Documents and Logs. 8.6.1.2.1 10/5/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Must provide and maintain MCP Doc. and Lags 8.6.1.4.1 10/5/2025