conversion
|
conversion
|
n/a
|
|
|
Must maintain car runby, Min. 6" currently 0".
|
10/14/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
MUST MAKE ALARM OPERABLE
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.3 Provide Auxiliary Lighting
|
x
|
|
MUST MAKE AUXILIARY LIGHTS OPERABLE
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
POWER BACK UP NOT WORKING / MISSING UNABLE TO LOWER UNIT WHEN POWER IS OFF
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Must perform and document monthly fire service testing. 8.6.11.1
|
10/5/2025
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current state operating cert. 5.100(2)
|
10/5/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Must provide and Maintain all required MCP Documents and Logs. 8.6.1.2.1
|
10/5/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Must provide and maintain MCP Doc. and Lags 8.6.1.4.1
|
10/5/2025
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Must provide current annual test tag on Mach. Room Fire Extinguisher. 8.11.2.1.2(j)
|
10/5/2025
|