MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. No phone line
|
4/19/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self-locking. (Can defeat from inside)
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Phone line dead. Emergency light and bell are working.
|
4/4/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Bldg line.
|
3/13/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.1 Electrical Equipment and Wiring
|
|
|
Machine room light is on motion sensor. Must be on manual switch
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.1 Electrical Equipment and Wiring
|
|
|
Machine room light is on a motion sensor. NEC 410.141 says light control must be externally operable.
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
|
|
Machine room has motion sensor switch.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
|
|
Hoistway door skins are loose, bowing out and rubbing hard opening and closing. Occasionally stall door.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
In car ffs key flaky. Works with effort. Needs replacement.
|
3/13/2025
|