Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. No phone line 4/19/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking. (Can defeat from inside)
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Phone line dead. Emergency light and bell are working. 4/4/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Machine room has motion sensor switch.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.8.1 Electrical Equipment and Wiring Machine room light is on a motion sensor. NEC 410.141 says light control must be externally operable.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.8.1 Electrical Equipment and Wiring Machine room light is on motion sensor. Must be on manual switch
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 Hoistway door skins are loose, bowing out and rubbing hard opening and closing. Occasionally stall door.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Bldg line. 3/13/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x In car ffs key flaky. Works with effort. Needs replacement. 3/13/2025