Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean up the oil spill in the pit. 6/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Repair or replace the pit light as it will not light. As it has water in the globe. Replace the wiring as it has been under water as well. 6/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean up the oil and water from the pit floor. 5/31/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Repair the non working sump pump or replace it. 6/14/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Replace the pit light fixture as it has been under water and is full of water at this time. It also does not work. 4/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Remove and dispose of the three buckets of used oil with water in it. It cannot be stored in the machine room. 4/30/2024
conversion conversion n/a need Current fire extinguisher in machine room 6/27/2018