Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.3 - Top-of-car operating device 8.11.2.1.3(c) Car top inspection switch is broken and shall be repaired or replaced. 10/18/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16 A capacity plate is missing inside the car. Plate shall state the capacity is 1400 lbs. 10/18/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting In cab emergency light and alarm bell shall work. 10/18/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational with 110v source removed. 8/18/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is working, establishes 2-way communication, but the answering agent cannot provide site location information. 2/9/2024