Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) x 2.20.2.2.1 Provide a rope data tag, and attach it to one of the shackles.
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) x 2.20.9.5.4 The rope retaining clips shall be located within 4x the diameter of the rope to the shackle and within 8x the diameter of the rope to the first clip.
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Suspension ropes are show rouge and the diameter has reduced beyond the maximum allowable amount. Replace suspension ropes. 11/25/2024