MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Access to the elevator disconnects shall be unobstructed
|
5/29/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Elevator disconnects room door shall be self closing and self locking
|
5/29/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
No flammable materials are to be stored in the elevator disconnect room
|
5/29/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency generator testing shall be performed. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
|
|
Sill guards are missing at the bottom of all hoistway door landings. Sills shall be the length of the leveling zone, plus 2 inches.
|
2/5/2020
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2 way communication not working, Re-inspect in 30 days
|
1/20/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written maintenance control program shall be kept on site for each elevator.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
8.11.2.1.3(s)
|
|
|
Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Counterweight runby is insufficient (3"), shorten hoisting belts to get 6" of runby.
|
2/24/2020
|
conversion
|
conversion
|
n/a
|
|
|
Repair Bottom Floor Trip hazard at hall sill
|
1/14/2020
|