Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)1 Access to the elevator disconnects shall be unobstructed 5/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator disconnects room door shall be self closing and self locking 5/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 No flammable materials are to be stored in the elevator disconnect room 5/29/2024
conversion conversion n/a Repair Bottom Floor Trip hazard at hall sill 1/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Repair Bottom Floor Trip hazard at hall sill. Previous violation from past years.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.11.2.1.3(s) Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.11.2.1.3(s) Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. Previous violations from past years.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Sill guards are missing at the bottom of all hoistway door landings. Sills shall be the length of the leveling zone, plus 2 inches. 2/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The counterweight sheave bearing is noticeably emanating noise that is indicative that the bearing has degraded and requires replacement.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication not working, Re-inspect in 30 days 1/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x Counterweight runby is insufficient (3"), shorten hoisting belts to get 6" of runby. 2/24/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency generator testing shall be performed. Re-inspection required 2/3/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency generator testing shall be performed. Re-inspection required.Previous violations from past years.