Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)1 Access to the elevator disconnects shall be unobstructed 5/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator disconnects room door shall be self closing and self locking 5/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 No flammable materials are to be stored in the elevator disconnect room 5/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Sill guards are missing at the bottom of all hoistway door landings. Sills shall be the length of the leveling zone, plus 2 inches. 2/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.11.2.1.3(s) Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x Counterweight runby is insufficient (3"), shorten hoisting belts to get 6" of runby. 2/24/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication not working, Re-inspect in 30 days 1/20/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency generator testing shall be performed. Re-inspection required
conversion conversion n/a Repair Bottom Floor Trip hazard at hall sill 1/14/2020