Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.11.2.1.3(s) Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency generator testing shall be performed. Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)1 Access to the elevator disconnects shall be unobstructed
MO Minimum : Elevators (H) - Machine Rooms (H)2 The door to the elevator disconnects shall be self closing & self locking
MO Minimum : Elevators (H) - Machine Rooms (H)4 No flammable materials are to be stored in the elevator disconnect room
conversion conversion n/a Repair Basement Floor Hall sill trip Hazard 7/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x Counterweights bottom out before car reaches its final limit. Repair 12/16/2019