Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide an MCP in machine room. 9/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lights and alarm not working, phone ok. 10/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide covers for fire service modules in machine room. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide guarding for overhead lighting in machine room. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Remove light timer in machine room and replace with conventional switch. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide guarding for overhead lighting in machine room. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) REMOVE motion sensor from machine room lighting circuit and replace with conventional switch. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Please provide an MCP, or location of MCP in machine room. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Remove all non elevator related items from machine room. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Provide covers for FFS modules in machine room. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Please post a Fire Service testing log in machine room, with monthly testing documented in log. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Please post current operating certificate in machine room. 9/23/2020