Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 3.4 Yes No The hoistway pit refuge space area is to be clearly and permanently marked and identified as "Refuge Space" and shall visible from the hoistway and entrance to the pit as required by the Missouri elevator safety board. 8/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 3.4 Yes No A sign with the words, "Danger Low Clearance," including the actual clearance dimension, shall be permanently posted on the power unit and shall be visible from within the pit and entrance to the pit as required by 3.4.1.6 and the Missouri elevator safety board. 8/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 3.4 Yes No Landing blocks and pipe stands shall be stored in the pit according to 8.6.4.7.2. 8/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Maintenance control program shall be in place. 8/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No The MCP shall not be stored on the top of the car. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 3.26.8 Pressure Switch Yes No Positive pressure switch is required as per 3.26.8 8/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19.4.1 No No The oil line shutoff shall be accessible from outside the hoistway. - Re-Inspection Required 6/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.4 No No Manual lowering shall be accessible from outside the hoistway. - Re-Inspection Required 6/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 No No Pressure gauge shall be accessible from outside the hoistway. - Re-Inspection Required 6/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an overspeed valve that is unsealed. A category 5 test shall be performed on the valve on or before the next annual inspection. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emegency phone shall establish 2-way communication. 12/30/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emergency phone shall establish two-way communication. 3/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes Yes The emergnecy phone shall establish 2-way communication. 3/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No The in car emergency lighting shall be operational. 4/19/2021