Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Please provide an MCP, or location of MCP at controller. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Please provide a Fire Service testing log, or location of testing log at controller, with monthly testing documented in log. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19.4.1 Provide a manual shut off valve outside of hoistway for main hydraulic line. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 3.26.8 Pressure Switch Provide pressure switch inline between cylinders and main valve. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 Provide a pressure guage fitting and shut off outside of hoistway. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.4 Provide manual lowering device outside of hoistway. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Please provide one type ABC fire extinguisher at the 2nd landing, near elevator door. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Oil in pit. 7/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide an MCP in machine room. 7/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 3.4 x Minimum refuge space inadequate, note clearance on top of pump unit, with letters and numbers 2" in height, visible from landing. 6/2/2021