ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Please provide an MCP, or location of MCP at controller.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Please provide a Fire Service testing log, or location of testing log at controller, with monthly testing documented in log.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19.4.1
|
|
|
Provide a manual shut off valve outside of hoistway for main hydraulic line.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.37 - Pressure Switch
|
3.26.8 Pressure Switch
|
|
|
Provide pressure switch inline between cylinders and main valve.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.5
|
|
|
Provide a pressure guage fitting and shut off outside of hoistway.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.4
|
|
|
Provide manual lowering device outside of hoistway.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Please provide one type ABC fire extinguisher at the 2nd landing, near elevator door.
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Oil in pit.
|
7/17/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide an MCP in machine room.
|
7/17/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
3.4
|
x
|
|
Minimum refuge space inadequate, note clearance on top of pump unit, with letters and numbers 2" in height, visible from landing.
|
6/2/2021
|