ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.7 - Car door or gate
|
2.14.4
|
No
|
No
|
The gate switch on the elevator car door shall be adjusted so that when the door is in the closed position, the gap between the leading edge of the door and the strike jamb is no more than 2 inches.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
Yes
|
No
|
The counterweight is touching the oil buffer when the elevator travels to the top floor. Hoist ropes should be shortened to provide a minimum runby of 6 inches. Re-inspection required
|
3/9/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
Yes
|
No
|
Full load test incomplete.
|
7/23/2021
|