Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes No Upper directional limit not working. Final limit ok. 1/21/2020
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes No Lower directional limit not working, final limit ok. 1/21/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No mach room door not self locking 1/1/2025
MO Minimum : Elevators (I) - Pits (I)3 Yes No Water in pit. Repair sump pump
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no curren cirt displayed 7/17/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt. displayed 7/17/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt. displayed 1/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No no fire extinquishe in machroom 7/17/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No door restrictors need adjustment 8/16/2023
A17.1-2016 : Elevators 5.3 - Final and emergency terminal stopping devices 8.6.4.19.5 (Normal and Final Terminal Stopping Devices) Yes No bottom dir. limit needs adjustment 8/16/2023