A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
|
|
sheetrock screws projection into the hoistway deed to be cut off flush to the wall
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
2.29.1
|
|
|
Label pit equipment with unit number - Multiple units (duplex)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
8.6.1.6.2
|
x
|
|
2.7.6.3.4 Governor remote trip is not working, car riding governor without access needs to have remote trip working
|
12/10/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel
|
|
|
in fire service phase 2 the rear door close button doesn't operate the rear door, the rear door can be closed using the front door close button. the rear door open button does operate the rear door. Make it so that the rear door close button operates the rear door.
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
x
|
|
the button labeled "rear door close" doesn't work on fire service phase 2, the front door close button closes both the front and rear doors
|
1/6/2023
|