Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Yes No the button labeled "rear door close" doesn't work on fire service phase 2, the front door close button closes both the front and rear doors 1/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.6.1.6.2 Yes No 2.7.6.3.4 Governor remote trip is not working, car riding governor without access needs to have remote trip working 12/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.2.3.1 Yes Yes perform full load portion of 5 year test elev company unable to perform as scheduled
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No MCP needed to be onsite with maint records and test procedures
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel No No in fire service phase 2 the rear door close button doesn't operate the rear door, the rear door can be closed using the front door close button. the rear door open button does operate the rear door. Make it so that the rear door close button operates the rear door. 12/1/2022
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 No No sheetrock screws projection into the hoistway deed to be cut off flush to the wall 6/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 No No Label pit equipment with unit number - Multiple units (duplex) 6/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 No No screws in hoistway sticking out from drywall need to break off
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 No No pit equip needs to be # to identify