Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel No No on fire service phase 2 the rear door close button does not operate the rear door, the front door close button does operate the rear door. the rear door open button does operate the rear door. Make it so that the rear door close button operates the rear door. 12/1/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 No No sheetrock screws projecting into the hoistway need to be cut off flush to the wall 6/10/2026
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 No No exposed drywall screws need to be broken off flush
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No need MCP onsite whicjh includes maint records and test procedures
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.2.3 Yes No 2.7.6.3.4 Governor remote trip is not working, car riding governor without access needs to have remote trip working 12/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Yes No the button labeled "rear door close" does not work, the button labeled "front door close" closes both the front and rear 1/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 No No Label pit equipment with unit number - multiple elevators (duplex) 6/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 No No # pit equipment mult hoistways
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.2.3.1 Yes Yes must perform full load portion of 5 yr test required