Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Remove maintenance control plan and prints from the top of the car 12/10/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 12/10/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not working 4/11/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair emergency light in the car 2/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.6.1.6.3 Remove prints from the top of the car and provide a secure container outside the hoistway 4/11/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide a complete maintenance control program 4/11/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(d) Need a maintenance control program on site posted on controller by or on next test date 2/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service & document on login machine room 1/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 All electric in pits 48" and below, shall be NEMA4 watertight 3/12/2019