Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.16 - Traveling cables and junction boxes 2.8.1 2.8.1.1 - Raceway shall be used to run the traveling cable through the machine room wall and into the machine room controller. Note: Currently the traveling cable is running through the machine room wall and into the machine room controller in it's original sheath, without the use of a raceway.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing The overspeed valve is not sealed. It shall be tested with the rated load on or before the next annual test per MO AHJ.