| ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) |  |  | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/28/2022 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x |  | The in car emergency lighting shall be operational. | 12/27/2021 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x |  | The in car emergency lighting shall be operational. | 2/7/2022 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | The in car emergency alarm bell shall be operational. | 2/7/2022 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.41 - Maintenance Records | 8.6.1.4 |  |  | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log & evacuation procedures. Fire service log to be recorded monthly. | 11/22/2024 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.31 - Relief Valves | 3.19.4.2 (Pump Relief Valve) | x |  | Relief valve setting shall be adjusted to properly meet OEM label on tank (FL= 350 psi, Bypass = 435 psi) but not more than 125% of the full load working pressure. | 10/18/2024 |