ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The emergency phone shall be operational.
|
5/2/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car telephone shall be operational.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
This elevator is equipped with an overspeed valve and is due for full load in 2021 or 2022.
|
3/10/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
No
|
No
|
The machine room door shall be self-locking and self-closing.
|
6/16/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
No
|
No
|
Keys shall be used to unlock the machine room from the outside. (Currently using a screw driver).
|
6/16/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
No
|
No
|
The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
3/10/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
No
|
No
|
Remove non-elevator material in machine room. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room.
|
3/10/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
No
|
No
|
The machine room temperature shall be kept within the manufacturers recommended rang.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
No
|
No
|
The fire extinguisher in the machine room is expired.
|
3/10/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
No
|
No
|
he car-top is showing obvious signs of corrosion. This appears to be caused by a leaking smoke control vent in the overhead. This shall be corrected as soon as possible to prevent further damage.
|
|
|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
In car phone does not work and shall be repaired and tested.
|
10/4/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Up to date operating certificate required in machine room.
|
3/10/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it.
|
|