ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
|
|
There is no State ID sticker or current operating certificate posted.
|
10/7/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working
|
9/22/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
|
|
Hoistway doors shall have appropriate floor numbers marked on hoistway side with numbers at least 4" tall on floors 1,2,3 & 4
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall provide 2 way communication with authorized personnel 24 hours a day. Re-inspection required
|
12/6/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall provide 2 way communications with persons able t take appropriate action 24/7. Re-inspection required
|
|
conversion
|
conversion
|
n/a
|
|
|
Hall door gap too wide on 2, 3, 4 floors.
|
10/7/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator has emergency generator backup power, which needs to be scheduled and tested within 60 days. Was noted on last year's inspection. Re-inspection required
|
|