ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.13.3.4
|
x
|
x
|
Install a metal cover over the sump pit in the elevator pit.
|
9/27/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Add a smoke detector in the machine room to recall the elevaator to the alternate floor and have tested and re-inspected
|
9/27/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Add a drip pan under the existing fire sprinkler main over the controller.
|
10/30/2018
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post updated certificate
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.3.1.2(b)
|
|
|
Machine room door is to be self closing
|
|