A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(d)
|
|
|
Maintenance Control Program does not comply with code. Missing maintenance procedures.
|
11/22/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
|
|
Emergency power hall indicator lights up during Firefighters' Service Phase I recall.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power lobby indicator light does not illuminate when elevator is transferred to standby power.
|
12/18/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection)
|
x
|
|
Firefighters' Service Phase I visual hall indicator lights up when elevator is on emergency power.
|
10/8/2024
|