Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power lobby indicator light does not illuminate when elevator is transferred to standby power. 12/18/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 Emergency power hall indicator lights up during Firefighters' Service Phase I recall.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) x Firefighters' Service Phase I visual hall indicator lights up when elevator is on emergency power. 10/8/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(d) Maintenance Control Program does not comply with code. Missing maintenance procedures. 11/22/2022