Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.1.2(bb) Yes No test tag on governor missing. 1/9/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide testing of the elevator on emergency power.
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) Yes No Provide testing of the elevator emergency power selector switch (fire control room)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No open electric boxes. 5/24/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator on emergency generator power operation. Re-inspection required 4/4/2025
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 No No Need to install code data plate with required information 3/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.14 - Hoistway clearances 8.11.2.1.3(t) No No landing head hitting final limit switch 5/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency Power shall be tested. 3/2/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not operable, needs repaired. Re-inspection required 4/4/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 2/4/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency evacuation system needs battery replaced. Re-inspection required 3/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - n/a n/a No No Clean elevator pit. 5/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be on display in the machine room 3/20/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 3/2/2026