A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage)
|
No
|
No
|
Phase I halo is worn and unreadable.
|
|
|
A17.1-2016 : Elevators
|
11.10 - Governor, Overspeed Switch
|
2.18.6.5
|
Yes
|
No
|
Means (solenoid) to remote activation of governor not working properly.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Provide testing of the elevator on emergency power.
|
|
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Provide testing of the elevator emergency power selector switch (fire control room).
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Emergency evacuation system needs battery pack replaced. Re-inspection required
|
3/6/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current state operating certificate shall be on display in the machine room
|
3/20/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Emergency Power shall be tested.
|
3/2/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
Yes
|
No
|
governor remote trip in controller does not work.
|
1/9/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
Yes
|
No
|
provide test tag on governor showing date of acceptance test.
|
1/9/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
Yes
|
Yes
|
counterweight governor switch does not work. red tag.
|
1/9/2019
|