Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency evacuation system needs battery pack replaced. Re-inspection required 3/6/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide testing of the elevator on emergency power.
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) Yes No Provide testing of the elevator emergency power selector switch (fire control room).
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be on display in the machine room 3/20/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) No No Phase I halo is worn and unreadable.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency Power shall be tested. 3/2/2026
A17.1-2016 : Elevators 11.10 - Governor, Overspeed Switch 2.18.6.5 Yes No Means (solenoid) to remote activation of governor not working properly.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 Yes No governor remote trip in controller does not work. 1/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 Yes No provide test tag on governor showing date of acceptance test. 1/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 Yes Yes counterweight governor switch does not work. red tag. 1/9/2019