A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
1/29/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet.
|
3/1/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required.
|
1/20/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete. Cellinoid that sets the overhead governor from machine space does not set the governor. Cellinoid needs to be repaired or replaced and full load safety test needs to be performed. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
x
|
|
Hoistway access switch not operating at the top and bottom floor. Re-inspection required
|
1/20/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.17.15
|
x
|
|
Governor remote trip/reset inoperable. Will not set the governor from machine room for testing, repair or replace. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
1/20/2026
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.10.2.2.1(r)
|
x
|
|
Door restriction missing flag / bracket on rear door. Re-inspection required
|
1/20/2026
|
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
2.13.4.2.3
|
x
|
|
Door closing force is greater than 30 lbs. Re-inspection required
|
1/20/2026
|