Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Hoistway access switch is not operating at top floor and bottom floor.
A17.1-2016 : Elevators 1.8 - Door closing force 2.13.4.2.3 x Door closing force is greater than 30 lbs. Re-inspection required
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 1/20/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 1/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet. 3/1/2024