Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.8 - Door closing force 2.13.4.2.3 x Door closing force is greater than 30 lbs. Re-inspection required
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x The elevator hoisting ropes are showing a high degree of wear / rouge and shall be replaced. Need to replace ropes within 30 days. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet. 3/1/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 1/29/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x The elevator hoisting ropes are showing a high degree of wear/rouge and shall be replaced. Replace ropes within 30 days of inspection. 1/29/2025