Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Clean hydraulic oil from pit floor.
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals x excessive leaking of hydraulic fluid at jack packing, repair as needed
MO Minimum : Elevators (I) - Pits (I)8 Pit sump hole shall be covered flush with the floor. The covering shall consist of a noncombustible material.
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Unit has hose returning hydraulic fluid directly to machine. Install 5 gallon catch can in pit to catch oil leakage.
conversion conversion n/a Water in elevator pit. All pits shall be kept dry, clean and free of equipment or material not relating to the operation of the elevator. Exception: Sump pumps. 1/19/2021