ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency battery lowering unit is inoperable. Repair or replace and reinspect
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Repair elevator pit lights. 12/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19.4.1 A manually operated shutoff valve shall be provided between the hydraulic machines and the hydraulic jack and shall be located outside the hoistway and adjacent to the hydraulic machine. 12/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.4 A manually operated valve, located on or adjacent to the control valve shall be provided and identified. 12/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 A pressure gauge fitting with shutoff valve shall be provided on jack side of the check valve. 12/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 3.26.8 Pressure Switch A pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder. 12/18/2019