conversion
|
conversion
|
n/a
|
|
|
Provide fire service instructions inside and outside elevator.
|
6/13/2023
|
conversion
|
conversion
|
n/a
|
|
|
elevator phone does not function.
|
6/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighter phase 1 instructions next to hall fire keyswitch. Presently has phase 2 instructions next to hall fire service keyswitch.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Cylinder drain lines run to hydraulic tank. Remove from tank and run to pit containers of no more than 5 gallons.
|
6/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighter phase 1 instructions next to hall firefighter keyswitch, not phase 2 instructions.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Cylinder drain lines run back to pumping unit. Cylinder drain lines need to be ran into pit collection containers. Each cylinder shall have a seperate collection container of no more than 5 gallon capacity.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Post In Case of Fire signage next to hall button fixture at each landing
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
No MCP
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
No MRL on site
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine room fire extinguisher certification has expired.
|
6/13/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
REMOVE ALL NON-ELEVATOR RELATED ITEMS FROM MACHINE ROOM
|
8/8/2024
|