Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not illuminate 4/12/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Install self-closing and self-locking machine room access door 4/12/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not operate 4/8/2024
MO Minimum : Elevators (I) - Pits (I)8 COVER HOLE IN PIT FLOOR 6/26/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 4/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No MCP 4/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MRL not up to date 4/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Replace broken button on bottom floor hall fixture. 4/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace broken firefighter keyswitch identification housing located on bottom floor hall fixture. 4/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace broken "Please Exit When Door Opens" jewel on car operating panel 4/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing 4/12/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly 4/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Cylinder drain line needs to drain into pit collection container 4/4/2024