Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x No emergency light or alarm
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate shall be located in a room where the Elevator Operating manuals and prints are located, which can be easily accessed. 8/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State Operating certificate needs to be kept with other documentation in a locked room 8/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 TKE needs tp supply maintenance control program. 8/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Proper Fire extinguisher needs to be maintained inn close access to machine control space. 8/9/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A Fire extinguisher shall be located by elevator control spaces outside hoistway coveniently accessed. 8/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Still need In Case of Fire signs at all floors but the 1st floor 8/9/2022
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Need In Case of Fire Signs posted at each floor by Hall call buttons 8/9/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Directioion arrows on entryway at each floor have been pushed in. Must be repaired 8/9/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit needs to be cleaned up. 8/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit needs to be cleaned. Pit recently had several feet of water. Oil in tank needs to be check for water contamination and rust removed from working parts of hydraulic machine in pit 8/9/2022