Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. | |||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | In car STOP switch is not rendered inoperative during Phase I recall | 5/17/2019 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Locate hear detector at top of hoistway within 24 in. of smoke detector | 5/17/2019 | |
MO Minimum : Elevators | (A) - Hoistways | (A)13 | Seal hoistway ceiling. Exposed wood ceiling joists | 11/4/2020 |