conversion
|
conversion
|
n/a
|
|
|
Provide fire service instructions inside and outside elevator.
|
2/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit. Cylinder drain line needs to be ran to pit container of no more than 5 gallons.
|
2/22/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove standing water from pit. Pits shall be kept dry and clean.
|
2/22/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test and log firefighter operation monthly
|
9/8/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit
|
9/8/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Replace plunger packing. Packing leaks excessively
|
9/8/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Firefighter instructions inside the elevator need to be for phase 2 operation not phase 1
|
9/8/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Firefighter instructions next to hall fire keyswitch need to be for phase 1 operation not phase 2
|
9/8/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit
|
2/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Replace plunger seal. Seal leaks excessively
|
2/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine room fire extinguisher certification is expired.
|
2/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
No MCP
|
2/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MRL not up to date
|
2/22/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
2/22/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
PROVIDE PHASE 2 FIRE SERVICE SIGNAGE
|
8/8/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Firefighter phase 2 operation does not override security for bottom floor car call. 14 days to repair or red tagged. May apply for variance from the state
|
9/8/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Firefighter phase 2 operation does not overide security for bottom floor car call. 14 days to correct or elevator will be red tagged.
|
8/23/2021
|