ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Sump hole filled with oil, remove. Determine if sump pump works, if not replace.
|
6/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
|
|
Machine room light plugged into outlet on ceiling. Fixture to be hard wired.
|
6/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Provide feeder location on main line disconnect. NEC 620.51(D)
|
6/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Provide feeder location on 110v. disconnect. In machine room. NEC620.51(D)
|
6/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean pit to remove debris, water and/or oil and address source
|
12/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean pit to remove debris, water and/or oil and address sources
|
12/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
7/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide MCP
|
6/17/2022
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
Expired ,tagged and sealed’16
|
12/9/2022
|