Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | Test incomplete, Full load safeties test, car & counterweight test, 125% buffer test, 125% brake test. Unintended motion up & down. Door pressure, Test emergency light, bell, & phone | 1/31/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | x | x | Drive machine brake is unable to hold 125% rated load. Re-inspection required, Red tagged | 1/4/2023 |